QJ4-25 type gas relay transformer Buchholz relay protector

Back to product >>
Cooperation Consulting >>

Product Details

Application

Buchholz relay type QJ is a kind of protective device used for oil immersed transformer with conservator and on-load tap changer. If a fault generated inside the transformer(or the on-load tap changer), cause gases generated from oil decomposed. When the amount of gas accumulate up to a stated level, the signal contact of buchholz relay turns on and send alarm signal. When a serious fault generates inside transformer or on-load tap changer, the transformer oil surge will happen, oil flow heavily in the pipeline and result in the operation of baffle plate of buchholz relay leads to the trip contact turning on, so trips the transformer. If the oil level is low due to the oil losses, the alarms is also initiated.

assembling method   the relay's pipe axis should be parallel to the transformer case cover,and it is allowed  for the end leading to the conservator is highter,however the inclination between the axis and level surface may not exceed 4%
 structure of the gas relay  the relay's core structure is shown in fig.1 and the relay's upper core consist of gas lock1,gas lock nut 2,probe 3,blocking 4,snap ring(float) 5,weight dro