Transformer Switch /off-Circuit Tap Changer (Bar Form)

Back to product >>
Cooperation Consulting >>

Product Details

General
This type of tap changer is comprised by tap changer body and operating mechanism. It is suitable for oil-
immersed power transformer with frequency of 50, 60Hz, rated voltage 35kV and 110kV, rated current from 200
to 1500A. The tap changer s installed on tanking body and operating on tank cover. They must be working
under non-energized condition.

Lead's section and length of the bar switch

Rated Current (A)   Lead's section mm2   Lead's Length (mm)
200 70 700
400 150
630 185
800 240
1000 (Double Lead) 185
1250(Double Lead) 185
1500(Double Lead) 240

Notice: If the customer has some special requirements, please detailed in ordering.

Technical parameters:

Type of tap changer Rated current (A) Rated
Voltage
(kV)
Range of voltage regulation No. of
phases
Regulating
positions
Install Dimension (mm) Holes on tank
cover (mm)
L L1 L2 H H1 ΦD
WDT II 200-400/35-4×3 200\400 35 ±5% 1 Middle part 656 396 72 73.5 24.5 Φ107 Φ80
WDT II 630-800/35-4×3 630\800 100 34 Φ127
WDT II 200-400/35-6×5 200\400 ±2×2.5% 800 540 72 73.5 24.5 Φ107
WDT II 630-800/35-6×5 630\800 100 34 Φ127
WDT II 200-400/35-8×7 200\400 ±3×2% 944 684 72 73.5 24.5 Φ107
WDT II 630-800/35-8×7 630\800 100 34 Φ127
WDT II 200-400/35-10×9 200\400 ±4×1.25% 1088 828 72 73.5 24.5 Φ107
WDT II 630-800/35-10×9 630\800 100 34 Φ127
WDT II 200-400/110-4×3 200\400 110 ±5% 728 468 96 73.5 24.5 Φ107
WDT II 630-800/110-4×3 630\800 100 34 Φ127
WDT II 200-400/110-6×5 200\400 ±2×2.5% 920 660 96 73.5 24.5 Φ107
WDT II 630-800/110-6×5 630\800 100 34 Φ127
WDT II 200-400/110-8×7 200\400 ±3×2% 1112 852 96 73.5 24.5 Φ107
WDT II 630-800/110-8×7 630\800 100 34 Φ127
WDT II 200-400/110-10×9 200\400 ±4×1.25% 1304 1044 96 73.5 24.5 Φ107
WDT II 630-800/110-10×9 630\800 100 34 Φ127


Company profile:
Main product line: Tap changer and HV switchgear
Tap changer manufacturing with fullest vertical integration
Tap Changer Products Range On-Load Tap Changer:
* Conventional OLTC for transformer with voltage up to 765kV
*Vacuum OLTC for oil transformer with voltage up to 765kV
*Vacuum OLTC for dry transformer with voltage of 72.5kV
Off-Circuit Tap Changer
* Application for the transformer with voltage up to 765kV

Our advantages:
Quality Assurance
--From the very beginning, VILLE ensures quality in every step to achieve the best quality.
 Experience Sharing
--With more than 30 years' experience in power industry, VILLE brings you an optimized solution.
 Global Service
--Wherever you are, VILLE global network will support and provide you with value.
 Quick Response
--In response to your needs without delay, VILLE  knows the value of your time.

Thanks for choosing VILLE as your reliable partner and
please trust both of us will create a brilliant future!

Related Products

PRODUCTS

Product consulting

Consulting products: *

Name: *

E-mail: *

Contact number: *

WeChat: *

Notes: *

控件[tem_25_34]渲染出错,Source:未将对象引用设置到对象的实例。