KYT8(KYN28A)- 24kv type Indoor metal armored central switchgear cabinet manufacturer supply

Back to product >>
Cooperation Consulting >>

Product Details

Kyt8 (kyn28a) - 24 indoor metal armored central switchgear (hereinafter referred to as switchgear) is a complete set of distribution equipment for 13.8-20kv three-phase AC 50 Hz single bus and single bus sectional system. It is mainly used for power transmission of power plants, small and medium generators, distribution of industrial and mining enterprises and secondary substation of power system. It is used for control, protection and monitoring. The switch cabinet meets the requirements of IEC298, GB3906 and other standards. It has the interlocking function of preventing the loaded push-pull circuit breaker hand, preventing the circuit breaker from mistakenly opening and closing, preventing the circuit breaker from closing when the grounding switch is in the closed position, preventing the circuit breaker from mistakenly entering the live compartment, and preventing the grounding switch from mistakenly closing when it is live. It can be equipped with vt19, VD4 and other vacuum circuit breakers. In fact, it is an excellent power distribution device.

Product features

a. The product is an assembled structural design, which is assembled by riveting nuts and high-strength bolts. The shell is made of 2mm thick aluminum zinc coated steel plate imported from Switzerland. The door plate is made of cold-rolled steel plate and resin powder electrostatic spraying process. It has beautiful appearance and convenient installation and maintenance.

b. The panel is processed and bended by CNC imported equipment, which makes the cabinet lighter than similar equipment in overall weight, good mechanical strength, IP4X protection grade of shell, high precision, easy to assemble and realize material unification.

c. Each high-voltage compartment is completely isolated, and each high-voltage compartment is equipped with its own pressure relief plate at the top of the cabinet, so as to ensure that the internal arc fault will not affect the adjacent compartments and ensure the safety of the equipment. Each high and low voltage compartment of the switch cabinet has good sealing measures, and the high voltage compartment is equipped with automatic heating device to ensure that the surface of the insulation body in the cabinet is dry.

d. It can close the door. The normal operation of the switch cabinet, including the opening and closing of the circuit breaker, the pushing of the circuit breaker handcart to the working position and the exit to the test / isolation device, and the opening and closing of the grounding switch, are required to be carried out under the opening and closing conditions of the high voltage compartment door plate.

e. The cabinet is divided into handcart room, bus room, cable room, relay and instrument room. The rear of the handcart room is equipped with a grounding metal valve, which automatically closes after the handcart is pulled out; the secondary contact can be connected and disconnected with the handcart; the bus room is separated from other rooms; the cable room is located in the lower part of the rear, which is convenient for laying in and out cables, and the grounding bus is installed at the bottom; the relay and instrument room are located in the front and upper part of the cabinet.

f. It can draw out horizontal partition board and partition board of loading and unloading bus room, so that the connection of main bus and the installation and maintenance of cable, grounding switch, arrester, current transformer and other components can be carried out on the front of switch cabinet, which is very convenient.

g. The panel of the switch cabinet is provided with an observation window, which can see the opening / closing button on the circuit breaker handcart, the mechanical position indicator of the circuit breaker and the energy storage / release status indicator of the spring, and can manually open / close the circuit breaker and the energy storage.

h. The insulation structure of the handcart and the cabinet is matched, and the mechanical interlocking is reliable and flexible. The handcart is equipped with disconnection, test and working positions in the cabinet, and positioning devices at each position to ensure reliable interlocking.

i. The live bus in the cabinet adopts heat shrinkable sleeve suit, the bus is made of copper material, and the lap joint is tinned.

Description 

Unit

Value

Rated voltage (maximum working voltage)

kV

24

Rated insulation level 1min power frequency withstand voltage

kV

65

Lightning impulse withstand voltage

kV

125

Rated frequency

Hz

50

Rated current of main bus

A

630,1250,1600,2000,2500,3150

Rated current of branch bus

A

630,1250,1600,2000,2500,3150

4S thermal stability current (RMS)

kA

16,20,25,31.5

Rated dynamic stability current (peak value)

kA

40,50,63,80

Protection level The enclosure is IP4X
Cabinet size (W * D * H)

mm

                                    1000×1900×2300                                