EP-3600/3750-HAN-UD/10~35
MV Turnkey Solution for 1500V Utility PV Plant
Central Inverter 3600/3750-HAN-UD/10~35 MV Turnkey Solution for 1500V Utility PV Plant
Utility-Scale PV Solutions
VILLE offers string inverter, central inverter and MV turnkey stations for utility-scale applications. With technical innovations and expertise in the field, We prioritizes enhancing product performance, efficiency, reliability, and safety. The company's primary goal is to make renewable energy accessible and cost-effective.
Central Inverter 3600/3750-HAN-UD/10~35 MV Turnkey Solution for 1500V Utility PV Plant
INPUT(AC)
OUTPUT(DC)
PROTECTION:
DC input protection Load break switch+fuse
Inverter output protection Circuit breaker
AC MV output protection Load Switch+Fuse
Overvoltage protection DC Type II/AC Type II
Leakage current monitoring Yes
Grid monitoring/Ground fault monitoring Yes/Yes
Insulation monitoring Yes
Overheat protection Yes
Night SVG function Yes
Anti-PID function Yes
AC input protection Fuse+disconnector
Transformer protection Oil-temperature, Oil-level, Oil-pressure and Buchholz
AC MV output protection Circuit breaker
LV Over-voltage protection Type II (Optional: Type I+II)
MV Relay Protection 50/51, 50N/51N, (Optional: 50G/51G)
Internal arcing fault IAC AFL 20kA/1s
TRANSFORMER
Transformer rated power 6250kVA
Transformer max. power 7250kVA
LV/MV Voltage 0.63-0.63/10~35kV
Transformer Vector Dy11y11
Transformer cooling type ONAN (Oil Natural Air Natural)
GENERAL DATA
Protection level | NEMA 4X(Electronic for inverter)/ NEMA 3R(Others) | |
Auxiliary power supply | Standard: 5kVA, Optional: Max. 40kVA | |
Temperature | -30~+ 60℃( >40℃ derating) | |
Allowed humidity(non condensing) | 0 ~ 95 % | |
Cooling method | Temperature controlled forced air cooling | |
Max.operating altitude | 1000m | |
Display | LCD | |
Communication port | RS485/Ethernet, Optional: optical fiber | |
Dimension(W*H*D) | 6058*2896*2438mm | |
Weight | 18t |
REFERENCE: